Abstract
Expressions for computing the external thermal resistance (T4 of buried cables, in both the IEEE and the IEC standards, are applicable to a limited number of installation geometries. In this paper, a method for the computation of T4 using the finite element approach is presented. With this method, a parametric study on how cable ampacity is affected by different configurations of the backfills is performed. The obtained results are compared with those of the IEC and IEEE standards (Neher-McGrath) and published extensions by El-Kady and Horrocks. Important differences can be observed for nonstandardized situations.
Original language | English (US) |
---|---|
Pages (from-to) | 537-543 |
Number of pages | 7 |
Journal | IEEE Transactions on Power Delivery |
Volume | 23 |
Issue number | 2 |
DOIs | |
State | Published - Apr 2008 |
Keywords
- Ampacity
- Backfill
- Cable thermal rating
- External thermal resistance
- Finite element method
- Neher-McGrath
- Underground cables
ASJC Scopus subject areas
- Energy Engineering and Power Technology
- Electrical and Electronic Engineering