TY - GEN
T1 - Improved Dynamic State Estimation Based Protection on VSC-HVDC Transmission Lines with Full Exploitation of Information Redundancy
AU - Jia, Yixiong
AU - Liu, Yu
AU - Lin, Yuzhang
AU - Wang, Binglin
N1 - Publisher Copyright:
© 2020 IEEE.
PY - 2020/8/2
Y1 - 2020/8/2
N2 - To ensure quick and reliable primary protection on VSCHVDC transmission lines, this paper proposes an improved Dynamic State Estimation (DSE) based protection method with full exploitation of information redundancy. The proposed approach improves the existing DSE based protection method by establishing a new dynamic model of the line under protection, which considers information redundancy embedded in the protection problem. The new dynamic model is systematically solved through the DSE procedure with weight matrices that are mathematically derived. Numerical experiments in an example VSC-HVDC system validate that the proposed DSE based protection method has improved selectivity, dependability and security compared to the existing DSE based protection method. In addition, the computation burden of the method is also carefully examined to ensure that it can meet real-time operation requirements of protective relays in practice.
AB - To ensure quick and reliable primary protection on VSCHVDC transmission lines, this paper proposes an improved Dynamic State Estimation (DSE) based protection method with full exploitation of information redundancy. The proposed approach improves the existing DSE based protection method by establishing a new dynamic model of the line under protection, which considers information redundancy embedded in the protection problem. The new dynamic model is systematically solved through the DSE procedure with weight matrices that are mathematically derived. Numerical experiments in an example VSC-HVDC system validate that the proposed DSE based protection method has improved selectivity, dependability and security compared to the existing DSE based protection method. In addition, the computation burden of the method is also carefully examined to ensure that it can meet real-time operation requirements of protective relays in practice.
KW - Dynamic state estimation based protection
KW - Information redundancy
KW - Transmission line protection
KW - VSC-HVDC transmission lines
UR - http://www.scopus.com/inward/record.url?scp=85099160423&partnerID=8YFLogxK
UR - http://www.scopus.com/inward/citedby.url?scp=85099160423&partnerID=8YFLogxK
U2 - 10.1109/PESGM41954.2020.9282057
DO - 10.1109/PESGM41954.2020.9282057
M3 - Conference contribution
AN - SCOPUS:85099160423
T3 - IEEE Power and Energy Society General Meeting
BT - 2020 IEEE Power and Energy Society General Meeting, PESGM 2020
PB - IEEE Computer Society
T2 - 2020 IEEE Power and Energy Society General Meeting, PESGM 2020
Y2 - 2 August 2020 through 6 August 2020
ER -