Improved insert geometry for reducing tank-wall losses in pad-mounted transformers

Juan Carlos Olivares, Rafael Escarela-Perez, S. V. Kulkarni, Francisco de León, Enrique Melgoza-Vasquez, Octavio Hernández-Anaya

Research output: Contribution to journalArticlepeer-review

Abstract

This paper presents a numerical analysis of losses generated in the tank-wall surrounding the high-current bushings of pad-mounted transformers using a three-dimensional (3-D) finite-element approach. Two cases are analyzed to study the impact of inserting small plates of different geometry (located near the high-current phases) on the reduction of tank losses. Significant reductions in stray losses occurring in the tank wall are obtained with plate inserts of low-cost. With the "T" configuration proposed in this paper, we reduce the tank-wall losses by a factor of 1/21 at rated current when compared with the case of tank wall without the stainless-steel plate. A 3-D time-harmonic finite-element model is used to determine the losses in the tank wall. Two load loss tests were carried out on experimental transformers to validate the simulations and effectiveness of the low-cost inserts.

Original languageEnglish (US)
Pages (from-to)1120-1126
Number of pages7
JournalIEEE Transactions on Power Delivery
Volume19
Issue number3
DOIs
StatePublished - Jul 2004

ASJC Scopus subject areas

  • Energy Engineering and Power Technology
  • Electrical and Electronic Engineering

Fingerprint

Dive into the research topics of 'Improved insert geometry for reducing tank-wall losses in pad-mounted transformers'. Together they form a unique fingerprint.