Abstract
In this letter, a new method is proposed to measure the magnetizing inductances of dual reversible models of single-phase two-winding transformers. Different from all available methods, a dc source is used to excite the transformer to produce deep-saturation through an air-core inductor. A small ac source is applied to the other winding to measure the two magnetizing inductances with only one test, significantly reducing the cost. The cost is further reduced because the necessary equipment is of smaller size than that for the available methods. The proposed method is validated experimentally and with finite elements simulations for two single-phase transformers.
Original language | English (US) |
---|---|
Article number | 9195156 |
Pages (from-to) | 488-491 |
Number of pages | 4 |
Journal | IEEE Transactions on Power Delivery |
Volume | 36 |
Issue number | 1 |
DOIs | |
State | Published - Feb 2021 |
Keywords
- Air-core inductance
- dual reversible model
- inrush currents
- saturation inductance
- transformer modeling